Specification of Digital RCD Tester Meter 5406A Merk Kyoritsu / Insulation Tester
Digital RCD Tester Meter Type 5406A Kyoritsu . Brand
• Custom microprocessor controlled for highest accuracy and reliability.
• 3 LEDs to check correct cable status.
• 0 and 180 degree phase angle switches allow for fast tests and consistent readings.
• Digital reading of tripping time.
• A constant current source circuit ensures that voltage fluctuations do not affect the accuracy of readings.
• Large custom digital display readout.
• Visual indication of reversed phase and neutral wire in socket.
• Designed for IP54 Rating.
• Complies with IEC 61557
• Large type RCD test: Standard, Selective, AC and A (DC sensitive breaker)
Rated Tripping Current 10/20/30/200/300/500mA
Error Condition Settings × 1/2, × 1, × 5, × DC,
AUTO RAMP
Current Trip Duration 1000ms, 200ms (×5)
Lowest Resolution 1ms
Travel Time Accuracy ±0.6%rdg±4dgt
Operating Voltage 230V+10%-15%
(195V - 253V) 50Hz
Safety Standard IEC 61557-1,-6
IEC 61010-1 CAT III 300V
IEC 61010-2-031 Pollution Level 2
Withstand Voltage 3700V AC for 1 minute
IP Rating IEC 60529-IP54
Dimensions 167(L) × 186(L) × 89(D)mm
Weight about 800g
Accessories Molded plug test cable*
9121 (Shoulder Strap)
9147 (Cable case)
Instruction manual
Optional 7121B (Simplified measuring probe)
* 7123 (AU): Australian plug
7124 (UK): UK plug (13A)
7125 (EU): European SHUKO Plug
7126 (SA): South African plug